bs6724 XLPE insulated cable structure and fire protection standard
Power Cable
Power cables are mainly used for power transmission and distribution purpose. It is an assembly of one or more individually insulated electrical conductors, usually held together with an overall sheath. The assembly is used for transmission and distribution of electrical power. Electrical power cables may be installed as permanent wiring within buildings, buried in the ground and run overhead or exposed.……Including: rubber cable, welding cable, URD cable, XLPE insulated power calbe etc.
Bare Overhead Conductor
Bare Overhead Conductors are used in overhead transmission and distribution network applications.They are also used for un-insulated hook ups, jumpers, grounding conductors and other applications. Our Conductors conform to ASTM, IEC, BS, BS EN and DIN standards.…… Including: AAC conductor, AAAC conductor, ACSR conductor, ACAR conductor, AACSR conductor, etc.
Aerial Bundled Cable
Aerial bundled cables (also aerial bundled conductors or simply ABC) are overhead power lines using several insulated phase conductors bundled tightly together, usually with a bare neutral conductor. Our abc calbe conform to ASTM, IEC, SANS standards.……Including: abc cables, cvered line wire, service drop wire etc.
Conductor | Plain annealed copper, stranded meet with IEC(EN) 60228 class 2 |
---|---|
Insulation | Crosslinked polyethylene compounds(XLPE) |
Inner sheath | PVC |
Armor | Galvanized steel wire |
Outer sheath | Thermoplastic LSZH complexes, BS 7655-6 standard , Uv protection, hydrocarbon resistance, prevent oil, prevent rodents, termite resistance can be as options. |
bs6724 cable xlpe insulation cable fire protection standard:
Flame retardant (Single vertical cable test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
---|---|
Reduce the spread of fire (vertical installation cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24;VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;CEI 20-37/2-1; BS 6425-1* |
No corrosive gases | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;CEI 20-37/2-2; BS 6425-2* |
Minimum smoke release | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
Non-toxic harmful gases | NES 02-713; NF C 20-454 |
Physical properties and thermal properties:
Working temperature range (Fixed condition) | maximum 90°C for XLPE |
---|---|
Short circuit overload temperature can up to 250°C(5s) | |
Minimum bend radius | 10 × the total diameter |