JYTOP XLPE POWER CABLE

phone

Armoured cable 1.5mm – PVC insulation and sheath control cable

Leave a Reply

Your email address will not be published. Required fields are marked *

  • Power Cable

    Power Cable

    Power cables are mainly used for power transmission and distribution purpose. It is an assembly of one or more individually insulated electrical conductors, usually held together with an overall sheath. The assembly is used for transmission and distribution of electrical power. Electrical power cables may be installed as permanent wiring within buildings, buried in the ground and run overhead or exposed.……Including: rubber cable, welding cable, URD cable, XLPE insulated power calbe etc.

  • Bare Overhead Conductor

    Bare Overhead Conductor

    Bare Overhead Conductors are used in overhead transmission and distribution network applications.They are also used for un-insulated hook ups, jumpers, grounding conductors and other applications. Our Conductors conform to ASTM, IEC, BS, BS EN and DIN standards.…… Including: AAC conductor, AAAC conductor, ACSR conductor, ACAR conductor, AACSR conductor, etc.

  • Aerial Bundled Cable

    Aerial Bundled Cable

    Aerial bundled cables (also aerial bundled conductors or simply ABC) are overhead power lines using several insulated phase conductors bundled tightly together, usually with a bare neutral conductor. Our abc calbe conform to ASTM, IEC, SANS standards.……Including: abc cables, cvered line wire, service drop wire etc.

  • Armoured cable 1.5mm - PVC insulation and sheath control cable
     
    Rated power-frequency voltage U0/U: 0.6/1 KV
     
    Max permissible continuous operating temperature of conductor 70℃.
     
    Max short-circuit temperature of the conductor shall not exceed (Max 5 seconds duration): cross-section of conductor  300 mm2.
     
    The anbient temperature under installations should not be below 0℃.
     
    The bending radius of single core cable should not be less than 20 times of the cable diameter, the bending radius of multi-core cable should not be less than 15 times of the cable diameter.
     
    Nominal cross-sectional areas: 1.5 mm2 , 2.5 mm2  ,4 mm2 , 6 mm2 , 10 mm2  , 16 mm2 ,25 mm2  , 35 mm2 , 50 mm2  ,70 mm2  , 95 mm2  ,120 mm2  ,150 mm2 ,185 mm2  ,240 mm2 ,300 mm2  400 mm2 500 mm2 630 mm2 800 mm2
     
    PVC insulation and sheath control cable model:
     
    KVVP
    Copper core PVC insulated PVC sheathed copper wire woven shield control cable
     
    KVVP2
    Copper core PVC insulated PVC sheathed copper tape shielded control cable
     
    KVV22
    Copper core PVC insulated PVC sheathed steel tape armoured control cable
     
    KVVR
    Copper conductor PVC insulated PVC sheathed control flexible cable
     
    KVVRP
    Copper core PVC insulated PVC sheathed copper wire woven shield flexible control cable
     
    KVVP2-22
    Copper core PVC insulated PVC sheathed copper tape shielding copper steel tape armoured control cable
     
    KVVP22
    Copper core PVC insulated PVC sheathed copper braid shield steel tape armoured control cable
     
    Armoured cable 1.5mm parameter:
     
    Norminal sectional area  Insulation thickness Sheath thickness(mm)

    Overal diameter

    of cable (mm)

    D.C resistance of conductor (km)                 Current rating
    in air(A) direct in soil(A)
    Cu Al Cu Al Cu Al
    1×1.5 0.7 1.5 6 <=12.1 <=12.1 30 25 45 35
    1×4 0.7 1.5 7 <=7.41 <=7.41 45 35 60 50
    1×6 0.7 1.5 7 <=3.08 <=4.61 55 45 70 55
    1×35 0.9 1.5 12 <=0.524 <=0.868 175 140 190 150
    1×50 1 1.5 13 <=0.387 <=0.641 210 170 225 180
    1×70 1.1 1.5 14 <=0.268 <=0.443 270 215 280 225
    1×95 1.1 1.5 16 <=0.193 <=0.320 340 275 335 270
    1×120 1.2 1.5 18 <=0.153 <=0.253 400 320 380 305
    1×150 1.4 2 21 <=0.124 <=0.206 460 370 425 340
    1×185 1.6 2 23 <=0.0991 <=0.164 530 415 480 375
    1×240 1.7 2 25 <=0.0754 <=0.125 625 490 555 435

    Pre:
    Next: MC armored cable - Interlocking metal clad armored cable