JYTOP XLPE POWER CABLE

phone

22 kv cable specification – 12.7/22KV Galvanized steel wire armoured electrical cables

Leave a Reply

Your email address will not be published. Required fields are marked *

  • Power Cable

    Power Cable

    Power cables are mainly used for power transmission and distribution purpose. It is an assembly of one or more individually insulated electrical conductors, usually held together with an overall sheath. The assembly is used for transmission and distribution of electrical power. Electrical power cables may be installed as permanent wiring within buildings, buried in the ground and run overhead or exposed.……Including: rubber cable, welding cable, URD cable, XLPE insulated power calbe etc.

  • Bare Overhead Conductor

    Bare Overhead Conductor

    Bare Overhead Conductors are used in overhead transmission and distribution network applications.They are also used for un-insulated hook ups, jumpers, grounding conductors and other applications. Our Conductors conform to ASTM, IEC, BS, BS EN and DIN standards.…… Including: AAC conductor, AAAC conductor, ACSR conductor, ACAR conductor, AACSR conductor, etc.

  • Aerial Bundled Cable

    Aerial Bundled Cable

    Aerial bundled cables (also aerial bundled conductors or simply ABC) are overhead power lines using several insulated phase conductors bundled tightly together, usually with a bare neutral conductor. Our abc calbe conform to ASTM, IEC, SANS standards.……Including: abc cables, cvered line wire, service drop wire etc.

  • 22 kv cable specification
    application:
     
    The cable is used as high-pressure feeder fixing conditions.
     
    structure:
    Galvanized steel wire armoured electrical cables
    Conductor: stranded copper conductor
     
    Insulation: XLPE
     
    Alone shield (ground): copper wire shielding
     
    Inner sheath: PVC jacket
     
    Armour: galvanized steel wire armoring
     
    Outer sheath: AS/NZS 1429.1 standard PVC jacket.
     
    12.7/22KV Galvanized steel wire armoured electrical cables parameter:
     
    Nominal conductor cross-sectional area Nominal diameter of the conductor Insulation thickness Conductor shielding Sheathed wire diameter Nominal thickness of sheath Nominal diameter Nominal weight
    Stranded specifications Shielding cross-sectional area
    mm² mm mm mm mm² mm mm mm kg/100m
    12.7/22kV
    35 6.8 5.5 14/0.85 7.9 2.5 2.9 63.2 600
    50 8.0 5.5 15/0.85 8.5 2.5 3.0 66.0 665
    70 9.6 5.5 21/0.85 11.9 2.5 3.1 69.9 775
    95 11.5 5.5 29/0.85 16.5 2.5 3.3 74.4 920
    120 13.1 5.5 36/0.85 20.4 3.15 3.4 79.5 1140
    150 14.5 5.5 44/0.85 25.0 3.15 3.5 83.1 1280
    185 16.1 5.5 22/1.35 31.5 3.15 3.7 89.1 1450
    240 18.5 5.5 29/1.35 41.5 3.15 3.9 95.0 1720
    300 20.7 5.5 37/1.35 53.0 3.15 4.1 101.1 2010
    400 23.6 5.5 47/1.35 67.3 3.15 4.3 108.2 2420